| − | This is the support page for the Air-Con | + | '''''The Multi Split Series was discontinued in Mid 2022. All information preserved here is for legacy support.''''' |
| − | [[File: Multi- | + | ---- |
| − | == Indoor Units == | + | This is the support page for the 22-21 SEER Air-Con Multi Split line. If you're looking for our 16 SEER models please visit the [[Air-Con Multi Split 16 SEER]] page. |
| − | * [[ | + | {{Infobox |
| − | * [[ | + | | |
| − | * [[ | + | | bodyclass = infobox |
| + | | name = Multi Split Series | ||
| + | | title = Multi Split Series | ||
| + | | subheader = Multi Zone Mini Split Line | ||
| + | | image = [[File:New-Multi-Logo.png|center|300px]] | ||
| + | |||
| + | | header1 = | ||
| + | | label1 = Voltage | ||
| + | | data1 = 220V | ||
| + | | header2 = | ||
| + | | label2 = SEER Rating | ||
| + | | data2 = 21-22 | ||
| + | | header3 = | ||
| + | | label3 = Capacities (Outdoor Unit) | ||
| + | | data3 = 18,000 - 42,000 BTU | ||
| + | | header4 = | ||
| + | | label4 = Capacities (Indoor Unit) | ||
| + | | data4 = 9,000 - 24,000 BTU | ||
| + | | header5 = | ||
| + | | label5 = Heat Pump? | ||
| + | | data5 = Yes | ||
| + | | header6 = | ||
| + | | label6 = Model Sold From | ||
| + | | data6 = June 2017 - July 2022 | ||
| + | }} | ||
| + | == Indoor Units (Wall Mount Type) == | ||
| + | * [[AMTEM4H4R09]] | ||
| + | * [[A16EW4H4R09]] (Legacy) | ||
| + | * [[AMTEM4H4R12]] | ||
| + | * [[A16EW4H4R12]] (Legacy) | ||
| + | * [[AMTEM4H4R18]] | ||
| + | * [[A16EW4H4R18]] (Legacy) | ||
| + | * [[A16EW4H4R24]] | ||
| + | |||
| + | == Indoor Units (Cassette Type) == | ||
| + | * [[A16EC4H4R12]] | ||
| + | * [[A16EC4H4R18]] | ||
| + | * [[A16EC4H4R24]] | ||
| + | == Indoor Units (Ducted Type)== | ||
| + | * [[A16EK4H4R12]] | ||
| + | * [[A16EK4H4R18]] | ||
| + | * [[A16EK4H4R24]] | ||
| + | == Indoor Units (Floor & Ceiling Type)== | ||
| + | * [[A16EL4H4R09]] | ||
| + | * [[A16EL4H4R12]] | ||
| + | * [[A16EL4H4R18]] | ||
| + | * [[A16EL4H4R24]] | ||
| + | |||
== Outdoor Units == | == Outdoor Units == | ||
| − | * [[ | + | * [[AMTCM4H4R18]] |
| − | * [[ | + | * [[AMTCM4H4R24]] |
| − | * [[ | + | * [[AMTCM4H4R30]] |
| − | * [[ | + | * [[AMTCM4H4R36]] |
| − | * [[ | + | * [[AMTCM4H4R42]] |
== Possible Combinations == | == Possible Combinations == | ||
These are the recommended indoor-outdoor unit combinations. | These are the recommended indoor-outdoor unit combinations. | ||
| Line 16: | Line 63: | ||
| Zones | | Zones | ||
| Outdoor Unit | | Outdoor Unit | ||
| + | | Indoor Units | ||
| + | | Indoor Units | ||
| + | | Indoor Units | ||
| Indoor Units | | Indoor Units | ||
| Indoor Units | | Indoor Units | ||
| Line 23: | Line 73: | ||
|- | |- | ||
| rowspan="2"| Dual Zone | | rowspan="2"| Dual Zone | ||
| − | | rowspan="2"| | + | | rowspan="2"| AMTCM4H4R18 |
| − | | | + | | A16EW4H4R09 |
| − | | | + | | A16EW4H4R09 |
| − | | | + | | A16EW4H4R18 |
| | | | ||
| | | | ||
|- | |- | ||
| − | | | + | | A16EW4H4R09 |
| − | | | + | | A16EW4H4R12 |
| | | | ||
| | | | ||
| Line 37: | Line 87: | ||
|- | |- | ||
| rowspan="3"| Tri Zone | | rowspan="3"| Tri Zone | ||
| − | | rowspan="3"| | + | | rowspan="3"| AMTCM4H4R24 |
| − | | | + | | A16EW4H4R09 |
| − | | | + | | A16EW4H4R09 |
| − | | | + | | A16EW4H4R12 |
| − | | | + | | A16EW4H4R09 |
| − | | | + | | A16EW4H4R18 |
|- | |- | ||
| − | | | + | | A16EW4H4R09 |
| − | | | + | | A16EW4H4R09 |
| − | | | + | | A16EW4H4R12 |
| − | | | + | | A16EW4H4R12 |
| | | | ||
|- | |- | ||
| − | | | + | | A16EW4H4R09 |
| | | | ||
| | | | ||
| Line 58: | Line 108: | ||
| rowspan="4"| Quad Zone | | rowspan="4"| Quad Zone | ||
| rowspan="4"| | | rowspan="4"| | ||
| − | * | + | * AMTCM4H4R30 |
| − | * | + | * AMTCM4H4R36 |
| − | | | + | | A16EW4H4R09 |
| − | | | + | | A16EW4H4R12 |
| − | | | + | | A16EW4H4R12 |
| − | | | + | | A16EW4H4R09 |
| − | | | + | | A16EW4H4R18 |
| + | |- | ||
| + | | A16EW4H4R09 | ||
| + | | A16EW4H4R12 | ||
| + | | A16EW4H4R12 | ||
| + | | A16EW4H4R09 | ||
| + | | A16EW4H4R18 | ||
| + | |- | ||
| + | | A16EW4H4R09 | ||
| + | | A16EW4H4R12 | ||
| + | | A16EW4H4R09 | ||
| + | | A16EW4H4R18 | ||
| + | | | ||
| + | |- | ||
| + | | A16EW4H4R09 | ||
| + | | | ||
| + | | | ||
| + | | | ||
| + | | | ||
|- | |- | ||
| − | | | + | | rowspan="5"| Quint Zone |
| − | | | + | | rowspan="5"| AMTCM4H4R42 |
| − | | | + | | A16EW4H4R09 |
| − | | | + | | A16EW4H4R12 |
| − | | | + | | A16EW4H4R09 |
| + | | A16EW4H4R09 | ||
| + | | A16EW4H4R09 | ||
| + | | A16EW4H4R12 | ||
| + | | A16EW4H4R18 | ||
| + | | A16EW4H4R09 | ||
|- | |- | ||
| − | | | + | | A16EW4H4R09 |
| − | | | + | | A16EW4H4R12 |
| − | | | + | | A16EW4H4R09 |
| − | | | + | | A16EW4H4R09 |
| + | | A16EW4H4R09 | ||
| + | | A16EW4H4R12 | ||
| + | | A16EW4H4R18 | ||
| + | | A16EW4H4R12 | ||
| + | |- | ||
| + | | A16EW4H4R09 | ||
| + | | A16EW4H4R12 | ||
| + | | A16EW4H4R12 | ||
| + | | A16EW4H4R12 | ||
| + | | A16EW4H4R09 | ||
| + | | A16EW4H4R12 | ||
| + | | A16EW4H4R12 | ||
| + | | A16EW4H4R18 | ||
| + | |- | ||
| + | | A16EW4H4R09 | ||
| + | | A16EW4H4R12 | ||
| + | | A16EW4H4R18 | ||
| + | | A16EW4H4R12 | ||
| + | | A16EW4H4R12 | ||
| + | | A16EW4H4R09 | ||
| + | | | ||
| | | | ||
|- | |- | ||
| − | | | + | | A16EW4H4R09 |
| + | | | ||
| + | | | ||
| | | | ||
| | | | ||
| | | | ||
| | | | ||
| + | | | ||
|- | |- | ||
|} | |} | ||
* ''Note: Each indoor unit combination is viewed as a column.'' | * ''Note: Each indoor unit combination is viewed as a column.'' | ||
* ''Note: Both quad zone outdoor units are capable of the same combinations but make your judgement on the correct one to use based on room size.'' | * ''Note: Both quad zone outdoor units are capable of the same combinations but make your judgement on the correct one to use based on room size.'' | ||
| + | * ''Note: There are more possible combinations than those listed above. Please use proper capacity judgment when making multi-split combinations.'' | ||
| + | |||
== Error Codes == | == Error Codes == | ||
{| class="wikitable" | {| class="wikitable" | ||
| − | + | | Error Code | |
| − | + | | Error Description | |
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | U8 |
| − | | | + | | Zero Cross Detection Circuit Malfunction (Indoor Unit) |
| − | |||
|- | |- | ||
| − | | | + | | C5 |
| − | | | + | | Malfunction Protection of Jumper Cap (Indoor Unit) |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | H6 |
| − | | | + | | Indoor Unit Motor Feedback (Indoor Unit) |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | F1 |
| − | + | | Indoor Ambient Temperature Sensor is Open/Short Circuited | |
| − | |||
| − | | / | ||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | F2 |
| − | + | | Indoor Evaporator Temperature Sensor is Open/Short Circuited | |
| − | |||
| − | | / | ||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | B5 |
| − | | | + | | Liquid Valve Temperature Sensor is Open/Short Circuited |
| − | | | + | |- |
| − | | | + | | B7 |
| − | | / | + | | Gas Valve Temperature Sensor is Open/Short Circuited |
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | P7 |
| − | + | | Modular Temperature Sensor is Open/Short Circuited | |
| − | |||
| − | | / | ||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| F3 | | F3 | ||
| − | | / | + | | Outdoor Ambient Temperature Sensor is Open/Short Circuited |
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | |||
| F4 | | F4 | ||
| − | | | + | | Outdoor Condenser Middle Pipe Temperature Sensor is Open/Short Circuited |
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | |||
| F5 | | F5 | ||
| − | | / | + | | Outdoor Discharge Temperature Sensor is Open/Short Circuited |
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | E6 |
| − | | | + | | Communication Malfunction |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | U1 |
| − | | | + | | Phase Current Detection Circuit Malfunction |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | P8 |
| − | | | + | | Module High Temperature Protection |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | F0 |
| − | | | + | | Insufficient Refrigeration System Protection |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | PU |
| − | | | + | | Capacitor Charging Malfunction |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | E1 |
| − | | | + | | High Pressure System Protection |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | E3 |
| − | | | + | | Lower Pressure System Protection |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | H3 |
| − | | | + | | Compressor Overload Protection |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | LP |
| − | | | + | | Indoor Units and Outdoor Units Are Incompatible |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | EE |
| − | | | + | | Memory Chip Malfunction |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | DN |
| − | | | + | | Wrong Connection of Communication Wire or Electronic Expansion Valve Malfunction |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | L3 |
| − | | | + | | Malfunction Protection of Outdoor Fan 1 |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | DD |
| − | | | + | | Wrong Connection of Communication Wire or Electronic Expansion Valve Malfunction Status Detected |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | E7 |
| − | | | + | | Mode Conflict |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | FO |
| − | | | + | | Refrigerant Recycling Mode |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | AL |
| − | | | + | | Cross Fan |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | H1 |
| − | | | + | | Defrosting or Oil Return in Heating Mode |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | LC |
| − | | | + | | Compressor Failed to Start |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | E4 |
| − | | | + | | Compressor High Discharge Temperature Protection |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | E8 |
| − | | | + | | Overload Protection |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | E5 |
| − | | | + | | Whole Unit Overcurrent Protection |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | P5 |
| − | | | + | | Compressor Phase Current Protection |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | H7 |
| − | | | + | | Compressor Desynchronizing |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | LD |
| − | + | | Compressor Phase-lacking/Phase-inverse Protection | |
| − | | / | ||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | H5 |
| − | | | + | | IPM Modular Protection |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | PL |
| − | | | + | | Direct Current Bus-Bar Low Voltage Protection |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | PH |
| − | | | + | | Direct Current Bus-Bar High Voltage Protection |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| − | | | + | | HC |
| − | | | + | | PFC Protection |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| + | | U7 | ||
| + | | 4-Way Valve Abnormal | ||
|} | |} | ||
| − | + | * ''Note: To change from Celsius to Fahrenheit, power down remote, hold mode and down for 5 seconds.'' | |
| + | == AHRI Certification Information == | ||
{| class="wikitable" | {| class="wikitable" | ||
| − | + | ! Model Number | |
| − | + | ! AHRI Number | |
| + | ! Certification Type | ||
|- | |- | ||
| − | | | + | | A16CM4H4R18 |
| − | | | + | | 6970608 |
| + | | Non-Ducted Indoor Units | ||
|- | |- | ||
| − | | | + | | A16CM4H4R24 |
| − | | | + | | 6970623 |
| + | | Non-Ducted Indoor Units | ||
|- | |- | ||
| − | | | + | | A16CM4H4R36 |
| − | | | + | | 6970636 |
| + | | Non-Ducted Indoor Units | ||
|- | |- | ||
| − | | | + | | A16CM4H4R39 |
| − | | | + | | 6332649 |
| + | | Non-Ducted Indoor Units | ||
|- | |- | ||
| − | | | + | | A16CM4H4R42 |
| − | | | + | | 7180449 |
| + | | Non-Ducted Indoor Units | ||
|- | |- | ||
| − | | | + | | AMTCM4H4R18 |
| − | | | + | | 10149864 |
| + | | Non-Ducted Indoor Units | ||
|- | |- | ||
| − | | | + | | AMTCM4H4R24 |
| − | | | + | | 10149867 |
| + | | Non-Ducted Indoor Units | ||
|- | |- | ||
| − | | | + | | AMTCM4H4R30 |
| − | | | + | | 10149870 |
| + | | Non-Ducted Indoor Units | ||
|- | |- | ||
| − | | | + | | AMTCM4H4R36 |
| − | | | + | | 10149873 |
| + | | Non-Ducted Indoor Units | ||
|- | |- | ||
| − | | | + | | AMTCM4H4R42 |
| − | | | + | | 10149876 |
| + | | Non-Ducted Indoor Units | ||
|- | |- | ||
| − | | | + | | AMTCM4H4R18 |
| − | | | + | | 10149865 |
| + | | Ducted Indoor Units | ||
|- | |- | ||
| − | | | + | | AMTCM4H4R24 |
| − | | | + | | 10149868 |
| + | | Ducted Indoor Units | ||
|- | |- | ||
| − | | | + | | AMTCM4H4R30 |
| − | | | + | | 10149871 |
| + | | Ducted Indoor Units | ||
|- | |- | ||
| − | | | + | | AMTCM4H4R36 |
| − | | | + | | 10149874 |
| + | | Ducted Indoor Units | ||
|- | |- | ||
| − | | | + | | AMTCM4H4R18 |
| − | | | + | | 10149866 |
| + | | Mixed Ducted and Non-Ducted Indoor Units | ||
|- | |- | ||
| − | | | + | | AMTCM4H4R24 |
| − | | | + | | 10149869 |
| + | | Mixed Ducted and Non-Ducted Indoor Units | ||
|- | |- | ||
| − | | | + | | AMTCM4H4R30 |
| − | | | + | | 10149872 |
| + | | Mixed Ducted and Non-Ducted Indoor Units | ||
|- | |- | ||
| − | | | + | | AMTCM4H4R36 |
| − | | | + | | 10149875 |
| − | + | | Mixed Ducted and Non-Ducted Indoor Units | |
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |- | ||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
|- | |- | ||
| + | | AMTCM4H4R42 | ||
| + | | 10149878 | ||
| + | | Mixed Ducted and Non-Ducted Indoor Units | ||
| + | |- | ||
|} | |} | ||
| + | ''For the AHRI documentation please visit the [https://www.ahridirectory.org/ AHRI Directory] website.'' | ||
| + | |||
== Document Downloads == | == Document Downloads == | ||
| − | *[[:File: | + | *[[:File:Multi_Split_22-21_SEER_Owners_Manual_18K.pdf|Outdoor Unit User Manual (18K)]] |
| − | *[[:File:Multi-IDU_user_manual.pdf|Indoor Unit User Manual]] | + | *[[:File:Multi_Split_22-21_SEER_Owners_Manual_24-36K.pdf|Outdoor Unit User Manual (24, 30, 36K)]] |
| − | *[ | + | *[[:File:Multi_Split_22-21_SEER_Owners_Manual_42K.pdf|Outdoor Unit User Manual (42K)]] |
| − | *[[:File:Multi-Split-IDU-Service-Manual.pdf|Indoor Unit Service Manual]] | + | *[[:File:Multi-IDU_user_manual.pdf|Indoor Unit (Wall Mount) User Manual]] |
| + | *[[:File:Multi_Split_22-21_SEER_Service_Manual_18-24K.pdf|Outdoor Unit Service Manual (18, 24K)]] | ||
| + | *[[:File:Multi_Split_22-21_SEER_Service_Manual_30-42K.pdf|Outdoor Unit Service Manual (30, 36, 42K)]] | ||
| + | *[[:File:Multi-Split-IDU-Service-Manual.pdf|Indoor Unit (Wall Mount) Service Manual]] | ||
| + | *[[:File:Air-Con_Multi-II_Submittal_Sheet.pdf|Multi Split Submittal Sheet]] | ||
| + | |||
== Warranty Information == | == Warranty Information == | ||
| − | Each Multi Split unit set has a warranty of | + | Each Multi Split unit set has a warranty of 5 years for parts and 7 years for the compressor. If you need more information, please visit the Air-Con [[Warranty Policy]] page. |
Latest revision as of 13:11, 24 July 2025
The Multi Split Series was discontinued in Mid 2022. All information preserved here is for legacy support.
This is the support page for the 22-21 SEER Air-Con Multi Split line. If you're looking for our 16 SEER models please visit the Air-Con Multi Split 16 SEER page.
| Multi Zone Mini Split Line | |
| Voltage | 220V |
|---|---|
| SEER Rating | 21-22 |
| Capacities (Outdoor Unit) | 18,000 - 42,000 BTU |
| Capacities (Indoor Unit) | 9,000 - 24,000 BTU |
| Heat Pump? | Yes |
| Model Sold From | June 2017 - July 2022 |
Indoor Units (Wall Mount Type)
- AMTEM4H4R09
- A16EW4H4R09 (Legacy)
- AMTEM4H4R12
- A16EW4H4R12 (Legacy)
- AMTEM4H4R18
- A16EW4H4R18 (Legacy)
- A16EW4H4R24
Indoor Units (Cassette Type)
Indoor Units (Ducted Type)
Indoor Units (Floor & Ceiling Type)
Outdoor Units
Possible Combinations
These are the recommended indoor-outdoor unit combinations.
| Zones | Outdoor Unit | Indoor Units | Indoor Units | Indoor Units | Indoor Units | Indoor Units | Indoor Units | Indoor Units | Indoor Units |
| Dual Zone | AMTCM4H4R18 | A16EW4H4R09 | A16EW4H4R09 | A16EW4H4R18 | |||||
| A16EW4H4R09 | A16EW4H4R12 | ||||||||
| Tri Zone | AMTCM4H4R24 | A16EW4H4R09 | A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R09 | A16EW4H4R18 | |||
| A16EW4H4R09 | A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R12 | ||||||
| A16EW4H4R09 | |||||||||
| Quad Zone |
|
A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R12 | A16EW4H4R09 | A16EW4H4R18 | |||
| A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R12 | A16EW4H4R09 | A16EW4H4R18 | |||||
| A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R09 | A16EW4H4R18 | ||||||
| A16EW4H4R09 | |||||||||
| Quint Zone | AMTCM4H4R42 | A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R09 | A16EW4H4R09 | A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R18 | A16EW4H4R09 |
| A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R09 | A16EW4H4R09 | A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R18 | A16EW4H4R12 | ||
| A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R12 | A16EW4H4R12 | A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R12 | A16EW4H4R18 | ||
| A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R18 | A16EW4H4R12 | A16EW4H4R12 | A16EW4H4R09 | ||||
| A16EW4H4R09 |
- Note: Each indoor unit combination is viewed as a column.
- Note: Both quad zone outdoor units are capable of the same combinations but make your judgement on the correct one to use based on room size.
- Note: There are more possible combinations than those listed above. Please use proper capacity judgment when making multi-split combinations.
Error Codes
| Error Code | Error Description |
| U8 | Zero Cross Detection Circuit Malfunction (Indoor Unit) |
| C5 | Malfunction Protection of Jumper Cap (Indoor Unit) |
| H6 | Indoor Unit Motor Feedback (Indoor Unit) |
| F1 | Indoor Ambient Temperature Sensor is Open/Short Circuited |
| F2 | Indoor Evaporator Temperature Sensor is Open/Short Circuited |
| B5 | Liquid Valve Temperature Sensor is Open/Short Circuited |
| B7 | Gas Valve Temperature Sensor is Open/Short Circuited |
| P7 | Modular Temperature Sensor is Open/Short Circuited |
| F3 | Outdoor Ambient Temperature Sensor is Open/Short Circuited |
| F4 | Outdoor Condenser Middle Pipe Temperature Sensor is Open/Short Circuited |
| F5 | Outdoor Discharge Temperature Sensor is Open/Short Circuited |
| E6 | Communication Malfunction |
| U1 | Phase Current Detection Circuit Malfunction |
| P8 | Module High Temperature Protection |
| F0 | Insufficient Refrigeration System Protection |
| PU | Capacitor Charging Malfunction |
| E1 | High Pressure System Protection |
| E3 | Lower Pressure System Protection |
| H3 | Compressor Overload Protection |
| LP | Indoor Units and Outdoor Units Are Incompatible |
| EE | Memory Chip Malfunction |
| DN | Wrong Connection of Communication Wire or Electronic Expansion Valve Malfunction |
| L3 | Malfunction Protection of Outdoor Fan 1 |
| DD | Wrong Connection of Communication Wire or Electronic Expansion Valve Malfunction Status Detected |
| E7 | Mode Conflict |
| FO | Refrigerant Recycling Mode |
| AL | Cross Fan |
| H1 | Defrosting or Oil Return in Heating Mode |
| LC | Compressor Failed to Start |
| E4 | Compressor High Discharge Temperature Protection |
| E8 | Overload Protection |
| E5 | Whole Unit Overcurrent Protection |
| P5 | Compressor Phase Current Protection |
| H7 | Compressor Desynchronizing |
| LD | Compressor Phase-lacking/Phase-inverse Protection |
| H5 | IPM Modular Protection |
| PL | Direct Current Bus-Bar Low Voltage Protection |
| PH | Direct Current Bus-Bar High Voltage Protection |
| HC | PFC Protection |
| U7 | 4-Way Valve Abnormal |
- Note: To change from Celsius to Fahrenheit, power down remote, hold mode and down for 5 seconds.
AHRI Certification Information
| Model Number | AHRI Number | Certification Type |
|---|---|---|
| A16CM4H4R18 | 6970608 | Non-Ducted Indoor Units |
| A16CM4H4R24 | 6970623 | Non-Ducted Indoor Units |
| A16CM4H4R36 | 6970636 | Non-Ducted Indoor Units |
| A16CM4H4R39 | 6332649 | Non-Ducted Indoor Units |
| A16CM4H4R42 | 7180449 | Non-Ducted Indoor Units |
| AMTCM4H4R18 | 10149864 | Non-Ducted Indoor Units |
| AMTCM4H4R24 | 10149867 | Non-Ducted Indoor Units |
| AMTCM4H4R30 | 10149870 | Non-Ducted Indoor Units |
| AMTCM4H4R36 | 10149873 | Non-Ducted Indoor Units |
| AMTCM4H4R42 | 10149876 | Non-Ducted Indoor Units |
| AMTCM4H4R18 | 10149865 | Ducted Indoor Units |
| AMTCM4H4R24 | 10149868 | Ducted Indoor Units |
| AMTCM4H4R30 | 10149871 | Ducted Indoor Units |
| AMTCM4H4R36 | 10149874 | Ducted Indoor Units |
| AMTCM4H4R18 | 10149866 | Mixed Ducted and Non-Ducted Indoor Units |
| AMTCM4H4R24 | 10149869 | Mixed Ducted and Non-Ducted Indoor Units |
| AMTCM4H4R30 | 10149872 | Mixed Ducted and Non-Ducted Indoor Units |
| AMTCM4H4R36 | 10149875 | Mixed Ducted and Non-Ducted Indoor Units |
| AMTCM4H4R42 | 10149878 | Mixed Ducted and Non-Ducted Indoor Units |
For the AHRI documentation please visit the AHRI Directory website.
Document Downloads
- Outdoor Unit User Manual (18K)
- Outdoor Unit User Manual (24, 30, 36K)
- Outdoor Unit User Manual (42K)
- Indoor Unit (Wall Mount) User Manual
- Outdoor Unit Service Manual (18, 24K)
- Outdoor Unit Service Manual (30, 36, 42K)
- Indoor Unit (Wall Mount) Service Manual
- Multi Split Submittal Sheet
Warranty Information
Each Multi Split unit set has a warranty of 5 years for parts and 7 years for the compressor. If you need more information, please visit the Air-Con Warranty Policy page.