Difference between revisions of "Air-Con Multi Split"
From Technical Support Wiki
(27 intermediate revisions by the same user not shown) | |||
Line 1: | Line 1: | ||
− | This is the support page for the Air-Con | + | This is the support page for the 22-21 SEER Air-Con Multi Split line. If you're looking for our 16 SEER models please visit the [[Air-Con Multi Split 16 SEER]] page. |
− | [[File: Multi- | + | {{Infobox |
− | == Indoor Units == | + | | |
− | * [[ | + | | bodyclass = infobox |
− | * [[ | + | | name = Multi Split Series |
− | * [[ | + | | title = Multi Split Series |
+ | | subheader = Multi Zone Mini Split Line | ||
+ | | image = [[File:New-Multi-Logo.png|center|300px]] | ||
+ | |||
+ | | header1 = | ||
+ | | label1 = Voltage | ||
+ | | data1 = 220V | ||
+ | | header2 = | ||
+ | | label2 = SEER Rating | ||
+ | | data2 = 21-22 | ||
+ | | header3 = | ||
+ | | label3 = Capacities (Outdoor Unit) | ||
+ | | data3 = 18,000 - 42,000 BTU | ||
+ | | header4 = | ||
+ | | label4 = Capacities (Indoor Unit) | ||
+ | | data4 = 9,000 - 24,000 BTU | ||
+ | | header5 = | ||
+ | | label5 = Heat Pump? | ||
+ | | data5 = Yes | ||
+ | | header6 = | ||
+ | | label6 = Model Sold From | ||
+ | | data6 = June 2017 - Present | ||
+ | }} | ||
+ | == Indoor Units (Wall Mount Type) == | ||
+ | * [[AMTEM4H4R09]] | ||
+ | * [[A16EW4H4R09]] (Legacy) | ||
+ | * [[AMTEM4H4R12]] | ||
+ | * [[A16EW4H4R12]] (Legacy) | ||
+ | * [[AMTEM4H4R18]] | ||
+ | * [[A16EW4H4R18]] (Legacy) | ||
+ | * [[A16EW4H4R24]] | ||
+ | |||
+ | == Indoor Units (Cassette Type) == | ||
+ | * [[A16EC4H4R12]] | ||
+ | * [[A16EC4H4R18]] | ||
+ | * [[A16EC4H4R24]] | ||
+ | == Indoor Units (Ducted Type)== | ||
+ | * [[A16EK4H4R12]] | ||
+ | * [[A16EK4H4R18]] | ||
+ | * [[A16EK4H4R24]] | ||
+ | == Indoor Units (Floor & Ceiling Type)== | ||
+ | * [[A16EL4H4R09]] | ||
+ | * [[A16EL4H4R12]] | ||
+ | * [[A16EL4H4R18]] | ||
+ | * [[A16EL4H4R24]] | ||
+ | |||
== Outdoor Units == | == Outdoor Units == | ||
− | * [[ | + | * [[AMTCM4H4R18]] |
− | * [[ | + | * [[AMTCM4H4R24]] |
− | * [[ | + | * [[AMTCM4H4R30]] |
− | * [[ | + | * [[AMTCM4H4R36]] |
− | * [[ | + | * [[AMTCM4H4R42]] |
== Possible Combinations == | == Possible Combinations == | ||
These are the recommended indoor-outdoor unit combinations. | These are the recommended indoor-outdoor unit combinations. | ||
Line 26: | Line 71: | ||
|- | |- | ||
| rowspan="2"| Dual Zone | | rowspan="2"| Dual Zone | ||
− | | rowspan="2"| | + | | rowspan="2"| AMTCM4H4R18 |
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R18 |
| | | | ||
| | | | ||
|- | |- | ||
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R12 |
| | | | ||
| | | | ||
Line 40: | Line 85: | ||
|- | |- | ||
| rowspan="3"| Tri Zone | | rowspan="3"| Tri Zone | ||
− | | rowspan="3"| | + | | rowspan="3"| AMTCM4H4R24 |
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R18 |
|- | |- | ||
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R12 |
| | | | ||
|- | |- | ||
− | | | + | | A16EW4H4R09 |
| | | | ||
| | | | ||
Line 61: | Line 106: | ||
| rowspan="4"| Quad Zone | | rowspan="4"| Quad Zone | ||
| rowspan="4"| | | rowspan="4"| | ||
− | * | + | * AMTCM4H4R30 |
− | * | + | * AMTCM4H4R36 |
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R18 |
|- | |- | ||
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R18 |
|- | |- | ||
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R18 |
| | | | ||
|- | |- | ||
− | | | + | | A16EW4H4R09 |
| | | | ||
| | | | ||
Line 88: | Line 133: | ||
|- | |- | ||
| rowspan="5"| Quint Zone | | rowspan="5"| Quint Zone | ||
− | | rowspan="5"| | + | | rowspan="5"| AMTCM4H4R42 |
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R18 |
− | | | + | | A16EW4H4R09 |
|- | |- | ||
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R18 |
− | | | + | | A16EW4H4R12 |
|- | |- | ||
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R18 |
|- | |- | ||
− | | | + | | A16EW4H4R09 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R18 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R12 |
− | | | + | | A16EW4H4R09 |
+ | | | ||
+ | | | ||
|- | |- | ||
− | | | + | | A16EW4H4R09 |
| | | | ||
| | | | ||
Line 130: | Line 177: | ||
| | | | ||
| | | | ||
− | | | + | | |
− | |||
|- | |- | ||
|} | |} | ||
Line 140: | Line 186: | ||
== Error Codes == | == Error Codes == | ||
{| class="wikitable" | {| class="wikitable" | ||
− | + | | Error Code | |
− | + | | Error Description | |
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | U8 |
− | | | + | | Zero Cross Detection Circuit Malfunction (Indoor Unit) |
− | |||
|- | |- | ||
− | | | + | | C5 |
− | | | + | | Malfunction Protection of Jumper Cap (Indoor Unit) |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | H6 |
− | | | + | | Indoor Unit Motor Feedback (Indoor Unit) |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | F1 |
− | + | | Indoor Ambient Temperature Sensor is Open/Short Circuited | |
− | |||
− | | / | ||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | F2 |
− | + | | Indoor Evaporator Temperature Sensor is Open/Short Circuited | |
− | |||
− | |||
− | | / | ||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | B5 |
− | | | + | | Liquid Valve Temperature Sensor is Open/Short Circuited |
− | | | + | |- |
− | | | + | | B7 |
− | | / | + | | Gas Valve Temperature Sensor is Open/Short Circuited |
− | |||
− | |||
|- | |- | ||
− | | | + | | P7 |
− | + | | Modular Temperature Sensor is Open/Short Circuited | |
− | |||
− | |||
− | | / | ||
− | |||
− | |||
|- | |- | ||
− | |||
| F3 | | F3 | ||
− | | / | + | | Outdoor Ambient Temperature Sensor is Open/Short Circuited |
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | |||
| F4 | | F4 | ||
− | | | + | | Outdoor Condenser Middle Pipe Temperature Sensor is Open/Short Circuited |
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | |||
− | |||
− | |||
− | |||
− | |||
| F5 | | F5 | ||
− | | Outdoor | + | | Outdoor Discharge Temperature Sensor is Open/Short Circuited |
|- | |- | ||
− | | | + | | E6 |
− | | | + | | Communication Malfunction |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | U1 |
− | | | + | | Phase Current Detection Circuit Malfunction |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | P8 |
− | | | + | | Module High Temperature Protection |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | F0 |
− | | | + | | Insufficient Refrigeration System Protection |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | PU |
− | | | + | | Capacitor Charging Malfunction |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | E1 |
− | | | + | | High Pressure System Protection |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | E3 |
− | | | + | | Lower Pressure System Protection |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | H3 |
− | | | + | | Compressor Overload Protection |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | LP |
− | + | | Indoor Units and Outdoor Units Are Incompatible | |
− | |||
− | |||
− | |||
− | |||
− | | Outdoor | ||
|- | |- | ||
− | | | + | | EE |
− | | | + | | Memory Chip Malfunction |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | DN |
− | | | + | | Wrong Connection of Communication Wire or Electronic Expansion Valve Malfunction |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | L3 |
− | | | + | | Malfunction Protection of Outdoor Fan 1 |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | DD |
− | | | + | | Wrong Connection of Communication Wire or Electronic Expansion Valve Malfunction Status Detected |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | E7 |
− | | | + | | Mode Conflict |
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | FO |
− | | | + | | Refrigerant Recycling Mode |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | AL |
− | | | + | | Cross Fan |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | H1 |
− | | | + | | Defrosting or Oil Return in Heating Mode |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | LC |
− | | | + | | Compressor Failed to Start |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | E4 |
− | | | + | | Compressor High Discharge Temperature Protection |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | E8 |
− | | | + | | Overload Protection |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | E5 |
− | | | + | | Whole Unit Overcurrent Protection |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | P5 |
− | | | + | | Compressor Phase Current Protection |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | H7 |
− | | | + | | Compressor Desynchronizing |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | LD |
− | + | | Compressor Phase-lacking/Phase-inverse Protection | |
− | |||
− | | / | ||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | H5 |
− | | | + | | IPM Modular Protection |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | PL |
− | | | + | | Direct Current Bus-Bar Low Voltage Protection |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | PH |
− | | | + | | Direct Current Bus-Bar High Voltage Protection |
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | HC |
− | | | + | | PFC Protection |
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
+ | | U7 | ||
+ | | 4-Way Valve Abnormal | ||
|} | |} | ||
− | + | * ''Note: To change from Celsius to Fahrenheit, power down remote, hold mode and down for 5 seconds.'' | |
+ | == AHRI Certification Information == | ||
{| class="wikitable" | {| class="wikitable" | ||
− | + | ! Model Number | |
− | + | ! AHRI Number | |
− | + | ! Certification Type | |
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
− | | | + | | A16CM4H4R18 |
− | | | + | | 6970608 |
+ | | Non-Ducted Indoor Units | ||
|- | |- | ||
− | | | + | | A16CM4H4R24 |
− | | | + | | 6970623 |
+ | | Non-Ducted Indoor Units | ||
|- | |- | ||
− | | | + | | A16CM4H4R36 |
− | | | + | | 6970636 |
+ | | Non-Ducted Indoor Units | ||
|- | |- | ||
− | | | + | | A16CM4H4R39 |
− | | | + | | 6332649 |
+ | | Non-Ducted Indoor Units | ||
|- | |- | ||
− | | | + | | A16CM4H4R42 |
− | | | + | | 7180449 |
+ | | Non-Ducted Indoor Units | ||
|- | |- | ||
− | | | + | | AMTCM4H4R18 |
− | | | + | | 10149864 |
+ | | Non-Ducted Indoor Units | ||
|- | |- | ||
− | | | + | | AMTCM4H4R24 |
− | | | + | | 10149867 |
+ | | Non-Ducted Indoor Units | ||
|- | |- | ||
− | | | + | | AMTCM4H4R30 |
− | | | + | | 10149870 |
+ | | Non-Ducted Indoor Units | ||
|- | |- | ||
− | | | + | | AMTCM4H4R36 |
− | | | + | | 10149873 |
+ | | Non-Ducted Indoor Units | ||
|- | |- | ||
− | | | + | | AMTCM4H4R42 |
− | | | + | | 10149876 |
+ | | Non-Ducted Indoor Units | ||
|- | |- | ||
− | | | + | | AMTCM4H4R18 |
− | | | + | | 10149865 |
+ | | Ducted Indoor Units | ||
|- | |- | ||
− | | | + | | AMTCM4H4R24 |
− | | | + | | 10149868 |
+ | | Ducted Indoor Units | ||
|- | |- | ||
− | | | + | | AMTCM4H4R30 |
− | | | + | | 10149871 |
+ | | Ducted Indoor Units | ||
|- | |- | ||
− | | | + | | AMTCM4H4R36 |
− | | | + | | 10149874 |
+ | | Ducted Indoor Units | ||
|- | |- | ||
− | | | + | | AMTCM4H4R18 |
− | | | + | | 10149866 |
+ | | Mixed Ducted and Non-Ducted Indoor Units | ||
|- | |- | ||
− | | | + | | AMTCM4H4R24 |
− | | | + | | 10149869 |
+ | | Mixed Ducted and Non-Ducted Indoor Units | ||
|- | |- | ||
− | | | + | | AMTCM4H4R30 |
− | | | + | | 10149872 |
+ | | Mixed Ducted and Non-Ducted Indoor Units | ||
|- | |- | ||
− | | | + | | AMTCM4H4R36 |
− | | | + | | 10149875 |
− | + | | Mixed Ducted and Non-Ducted Indoor Units | |
− | |||
− | |||
− | |- | ||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
|- | |- | ||
+ | | AMTCM4H4R42 | ||
+ | | 10149878 | ||
+ | | Mixed Ducted and Non-Ducted Indoor Units | ||
+ | |- | ||
|} | |} | ||
+ | ''For the AHRI documentation please visit the [https://www.ahridirectory.org/ AHRI Directory] website.'' | ||
+ | |||
== Document Downloads == | == Document Downloads == | ||
− | *[[:File: | + | *[[:File:Multi_Split_22-21_SEER_Owners_Manual_18K.pdf|Outdoor Unit User Manual (18K)]] |
− | *[[:File:Multi-IDU_user_manual.pdf|Indoor Unit User Manual]] | + | *[[:File:Multi_Split_22-21_SEER_Owners_Manual_24-36K.pdf|Outdoor Unit User Manual (24, 30, 36K)]] |
− | *[ | + | *[[:File:Multi_Split_22-21_SEER_Owners_Manual_42K.pdf|Outdoor Unit User Manual (42K)]] |
− | *[[:File:Multi-Split-IDU-Service-Manual.pdf|Indoor Unit Service Manual]] | + | *[[:File:Multi-IDU_user_manual.pdf|Indoor Unit (Wall Mount) User Manual]] |
+ | *[[:File:Multi_Split_22-21_SEER_Service_Manual_18-24K.pdf|Outdoor Unit Service Manual (18, 24K)]] | ||
+ | *[[:File:Multi_Split_22-21_SEER_Service_Manual_30-42K.pdf|Outdoor Unit Service Manual (30, 36, 42K)]] | ||
+ | *[[:File:Multi-Split-IDU-Service-Manual.pdf|Indoor Unit (Wall Mount) Service Manual]] | ||
+ | *[[:File:Air-Con_Multi-II_Submittal_Sheet.pdf|Multi Split Submittal Sheet]] | ||
+ | |||
== Warranty Information == | == Warranty Information == | ||
− | Each Multi Split unit set has a warranty of | + | Each Multi Split unit set has a warranty of 5 years for parts and 7 years for the compressor. If you need more information, please visit the Air-Con [[Warranty Policy]] page. |
Latest revision as of 15:31, 16 March 2020
This is the support page for the 22-21 SEER Air-Con Multi Split line. If you're looking for our 16 SEER models please visit the Air-Con Multi Split 16 SEER page.
Multi Zone Mini Split Line | |
Voltage | 220V |
---|---|
SEER Rating | 21-22 |
Capacities (Outdoor Unit) | 18,000 - 42,000 BTU |
Capacities (Indoor Unit) | 9,000 - 24,000 BTU |
Heat Pump? | Yes |
Model Sold From | June 2017 - Present |
Indoor Units (Wall Mount Type)
- AMTEM4H4R09
- A16EW4H4R09 (Legacy)
- AMTEM4H4R12
- A16EW4H4R12 (Legacy)
- AMTEM4H4R18
- A16EW4H4R18 (Legacy)
- A16EW4H4R24
Indoor Units (Cassette Type)
Indoor Units (Ducted Type)
Indoor Units (Floor & Ceiling Type)
Outdoor Units
Possible Combinations
These are the recommended indoor-outdoor unit combinations.
Zones | Outdoor Unit | Indoor Units | Indoor Units | Indoor Units | Indoor Units | Indoor Units | Indoor Units | Indoor Units | Indoor Units |
Dual Zone | AMTCM4H4R18 | A16EW4H4R09 | A16EW4H4R09 | A16EW4H4R18 | |||||
A16EW4H4R09 | A16EW4H4R12 | ||||||||
Tri Zone | AMTCM4H4R24 | A16EW4H4R09 | A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R09 | A16EW4H4R18 | |||
A16EW4H4R09 | A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R12 | ||||||
A16EW4H4R09 | |||||||||
Quad Zone |
|
A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R12 | A16EW4H4R09 | A16EW4H4R18 | |||
A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R12 | A16EW4H4R09 | A16EW4H4R18 | |||||
A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R09 | A16EW4H4R18 | ||||||
A16EW4H4R09 | |||||||||
Quint Zone | AMTCM4H4R42 | A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R09 | A16EW4H4R09 | A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R18 | A16EW4H4R09 |
A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R09 | A16EW4H4R09 | A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R18 | A16EW4H4R12 | ||
A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R12 | A16EW4H4R12 | A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R12 | A16EW4H4R18 | ||
A16EW4H4R09 | A16EW4H4R12 | A16EW4H4R18 | A16EW4H4R12 | A16EW4H4R12 | A16EW4H4R09 | ||||
A16EW4H4R09 |
- Note: Each indoor unit combination is viewed as a column.
- Note: Both quad zone outdoor units are capable of the same combinations but make your judgement on the correct one to use based on room size.
- Note: There are more possible combinations than those listed above. Please use proper capacity judgment when making multi-split combinations.
Error Codes
Error Code | Error Description |
U8 | Zero Cross Detection Circuit Malfunction (Indoor Unit) |
C5 | Malfunction Protection of Jumper Cap (Indoor Unit) |
H6 | Indoor Unit Motor Feedback (Indoor Unit) |
F1 | Indoor Ambient Temperature Sensor is Open/Short Circuited |
F2 | Indoor Evaporator Temperature Sensor is Open/Short Circuited |
B5 | Liquid Valve Temperature Sensor is Open/Short Circuited |
B7 | Gas Valve Temperature Sensor is Open/Short Circuited |
P7 | Modular Temperature Sensor is Open/Short Circuited |
F3 | Outdoor Ambient Temperature Sensor is Open/Short Circuited |
F4 | Outdoor Condenser Middle Pipe Temperature Sensor is Open/Short Circuited |
F5 | Outdoor Discharge Temperature Sensor is Open/Short Circuited |
E6 | Communication Malfunction |
U1 | Phase Current Detection Circuit Malfunction |
P8 | Module High Temperature Protection |
F0 | Insufficient Refrigeration System Protection |
PU | Capacitor Charging Malfunction |
E1 | High Pressure System Protection |
E3 | Lower Pressure System Protection |
H3 | Compressor Overload Protection |
LP | Indoor Units and Outdoor Units Are Incompatible |
EE | Memory Chip Malfunction |
DN | Wrong Connection of Communication Wire or Electronic Expansion Valve Malfunction |
L3 | Malfunction Protection of Outdoor Fan 1 |
DD | Wrong Connection of Communication Wire or Electronic Expansion Valve Malfunction Status Detected |
E7 | Mode Conflict |
FO | Refrigerant Recycling Mode |
AL | Cross Fan |
H1 | Defrosting or Oil Return in Heating Mode |
LC | Compressor Failed to Start |
E4 | Compressor High Discharge Temperature Protection |
E8 | Overload Protection |
E5 | Whole Unit Overcurrent Protection |
P5 | Compressor Phase Current Protection |
H7 | Compressor Desynchronizing |
LD | Compressor Phase-lacking/Phase-inverse Protection |
H5 | IPM Modular Protection |
PL | Direct Current Bus-Bar Low Voltage Protection |
PH | Direct Current Bus-Bar High Voltage Protection |
HC | PFC Protection |
U7 | 4-Way Valve Abnormal |
- Note: To change from Celsius to Fahrenheit, power down remote, hold mode and down for 5 seconds.
AHRI Certification Information
Model Number | AHRI Number | Certification Type |
---|---|---|
A16CM4H4R18 | 6970608 | Non-Ducted Indoor Units |
A16CM4H4R24 | 6970623 | Non-Ducted Indoor Units |
A16CM4H4R36 | 6970636 | Non-Ducted Indoor Units |
A16CM4H4R39 | 6332649 | Non-Ducted Indoor Units |
A16CM4H4R42 | 7180449 | Non-Ducted Indoor Units |
AMTCM4H4R18 | 10149864 | Non-Ducted Indoor Units |
AMTCM4H4R24 | 10149867 | Non-Ducted Indoor Units |
AMTCM4H4R30 | 10149870 | Non-Ducted Indoor Units |
AMTCM4H4R36 | 10149873 | Non-Ducted Indoor Units |
AMTCM4H4R42 | 10149876 | Non-Ducted Indoor Units |
AMTCM4H4R18 | 10149865 | Ducted Indoor Units |
AMTCM4H4R24 | 10149868 | Ducted Indoor Units |
AMTCM4H4R30 | 10149871 | Ducted Indoor Units |
AMTCM4H4R36 | 10149874 | Ducted Indoor Units |
AMTCM4H4R18 | 10149866 | Mixed Ducted and Non-Ducted Indoor Units |
AMTCM4H4R24 | 10149869 | Mixed Ducted and Non-Ducted Indoor Units |
AMTCM4H4R30 | 10149872 | Mixed Ducted and Non-Ducted Indoor Units |
AMTCM4H4R36 | 10149875 | Mixed Ducted and Non-Ducted Indoor Units |
AMTCM4H4R42 | 10149878 | Mixed Ducted and Non-Ducted Indoor Units |
For the AHRI documentation please visit the AHRI Directory website.
Document Downloads
- Outdoor Unit User Manual (18K)
- Outdoor Unit User Manual (24, 30, 36K)
- Outdoor Unit User Manual (42K)
- Indoor Unit (Wall Mount) User Manual
- Outdoor Unit Service Manual (18, 24K)
- Outdoor Unit Service Manual (30, 36, 42K)
- Indoor Unit (Wall Mount) Service Manual
- Multi Split Submittal Sheet
Warranty Information
Each Multi Split unit set has a warranty of 5 years for parts and 7 years for the compressor. If you need more information, please visit the Air-Con Warranty Policy page.