MHI VRF FDUM
From Technical Support Wiki
This is the support page for the Duct Connected Low/Middle Static Pressure indoor unit (FDUM) for MHI VRF air conditioners.
Duct Connected Low/Middle Static Pressure (FDUM) | |
Voltage | 220V |
---|---|
Capacities (kW) | 2.2-16.0 |
Heat Pump? | Yes |
Model Numbers
- FDUM22KXE6F
- FDUM28KXE6F
- FDUM36KXE6F
- FDUM45KXE6F
- FDUM56KXE6F
- FDUM71KXE6F
- FDUM90KXE6F
- FDUM112KXE6F
- FDUM140KXE6F
- FDUM160KXE6F
Specifications
Item | Unit | FDUM22KXE6F | FDUM28KXE6F | FDUM36KXE6F | FDUM45KXE6F | FDUM56KXE6F | FDUM71KXE6F | FDUM90KXE6F | FDUM112KXE6F | FDUM140KXE6F | FDUM160KXE6F | |
---|---|---|---|---|---|---|---|---|---|---|---|---|
Nominal Cooling Capacity | kW | 2.2 | 2.8 | 3.6 | 4.5 | 5.6 | 7.1 | 9.0 | 11.2 | 14.0 | 16.0 | |
Nominal Heating Capacity | kW | 2.5 | 3.2 | 4.0 | 5.0 | 6.3 | 8.0 | 10.0 | 12.5 | 16.0 | 18.0 | |
Power Source | 1 Phase 220V, 60Hz | |||||||||||
Power Consumption | Cooling | kW | 0.10 | 0.20 | 0.29 | 0.33 | 0.45 | |||||
Heating | 0.10 | 0.20 | 0.29 | 0.33 | 0.45 | |||||||
Sound Power Level | dB(A) | 60 | 65 | --- | ||||||||
Sound Pressure Level | dB(A) | Hi: 32 Me: 29 Lo: 26 | Hi: 33 Me: 29 Lo: 25 | Hi: 38 Me: 36 Lo: 30 | Hi: 40 Me: 34 Lo: 29 | Hi: 40 Me: 35 Lo: 30 | ||||||
Exterior Dimensions H x W x D | mm | 280x750x635 | 280x950x635 | 280x1370x740 | ||||||||
Net Weight | kg | 29 | 34 | 54 | ||||||||
Air Flow | m3/min | Hi: 10 Me: 9 Lo: 8 | Hi: 19 Me: 15 Lo: 10 | Hi: 28 Me: 25 Lo: 19 | Hi: 32 Me: 26 Lo: 20 | Hi: 35 Me: 28 Lo: 22 | ||||||
Maximum External Static Pressure | Pa | 100 | ||||||||||
Outside Air Intake | Possible | |||||||||||
Air Filter | Filter kit: UM-FL1EF/UM-FL2EF/UM-FL3EF (option) | |||||||||||
Remote Control (option) | wired: RC-EX3, RC-E5, RCH-E3 wireless: RCN-KIT4-E2 | |||||||||||
Refrigerant Piping Size | mm (in) | Liquid Line: ⌀6.35 (1/4") Gas Line: ⌀9.52 (3/8") | Liquid Line: ⌀6.35 (1/4") Gas Line: ⌀12.7 (1/2") | Liquid Line: ⌀9.52 (3/8") Gas Line: ⌀15.88 (5/8") |