MHI VRF FDTC
From Technical Support Wiki
This is the support page for the 4 way ceiling cassette (compact) indoor unit (FDTC) for MHI VRF air conditioners.
4 way Ceiling Cassette Compact (FDTC) | |
Voltage | 220V |
---|---|
Capacities (kW) | 1.5-5.6 |
Heat Pump? | Yes |
Model Numbers
- FDTC15KXE6F
- FDTC22KXE6F
- FDTC28KXE6F
- FDTC36KXE6F
- FDTC45KXE6F
- FDTC56KXE6F
Specifications
Item | Unit | FDTC15KXE6F | FDTC22KXE6F | FDTC28KXE6F | FDTC36KXE6F | FDTC45KXE6F | FDTC56KXE6F | |
---|---|---|---|---|---|---|---|---|
Nominal Cooling Capacity | kW | 1.5 | 2.2 | 2.8 | 3.6 | 4.5 | 5.6 | |
Nominal Heating Capacity | kW | 1.7 | 2.5 | 3.2 | 4.0 | 5.0 | 6.3 | |
Power Source | 1 Phase 220v, 60Hz | |||||||
Power Consumption | Cooling | kW | 0.02 | 0.03 | 0.05 | |||
Heating | 0.02 | 0.03 | 0.05 | |||||
Sound Power Level | dB(A) | 56 | 58 | 60 | ||||
Sound Pressure Level | Cooling | dB(A) | Hi: 32 Me: 28 Lo: 25 | Hi: 35 Me: 33 Lo: 30 | Hi: 38 Me: 36 Lo: 31 | Hi: 40 Me: 37 Lo: 31 | Hi: 45 Me: 39 Lo: 31 | |
Heating | Hi: 32 Me: 28 Lo: 25 | Hi: 35 Me: 33 Lo: 32 | Hi: 38 Me: 36 Lo: 34 | Hi: 40 Me: 37 Lo: 34 | Hi: 45 Me: 39 Lo: 34 | |||
Exterior Dimensions H x W x D | mm | Unit: 248x570x570 Panel: 35x700x700 | ||||||
Net Weight | kg | Unit: 14 Panel: 3.5 | Unit: 15 Panel: 3.5 | |||||
Air Flow | Cooling | m3/min | Hi: 7 Me: 5.5 Lo: 4.5 | Hi: 9.5 Me: 8.5 Lo: 7 | Hi: 10 Me: 9 Lo: 7 | Hi: 11 Me: 9 Lo: 7 | Hi: 13 Me: 10 Lo: 7 | |
Heating | Hi: 7 Me: 5.5 Lo: 4.5 | Hi: 9.5 Me: 8.5 Lo: 8 | Hi: 10 Me: 9 Lo: 8 | Hi: 11 Me: 9 Lo: 8 | Hi: 13 Me: 10 Lo: 8 | |||
Outside Air Intake | Possible with OA Spacer TC-OAS-E & Joint Duct TC-OAD-E | |||||||
Panel | TC-PSA-25W-E | |||||||
Air Filter, Qty | Pocket Plastic net x 1 (Washable) | |||||||
Remote Control (option) | wired: RC-EX3, RC-E5, RCH-E3 wireless: RCN-TC-24W-E2 | |||||||
Refrigeration Piping Size | mm(in) | Liquid Line: ⌀6.35 (1/4") Gas Line: ⌀9.52 (3/8") | Liquid Line: ⌀6.35 (1/4") Gas Line: ⌀12.7 (1/2") |