MHI KXZ ODU6
From Technical Support Wiki
This is the support page for the Heat Pump outdoor units for MHI VRF air conditioners.
Heat Pump Systems (FDC) | |
Voltage | 220V |
---|---|
Capacities (kW) | 73.5-112.0 |
Heat Pump? | Yes |
Model Numbers
- FDC735KXZE1M (FDC335 + FDC400)
- FDC800KXZE1M (FDC400 + FDC400)
- FDC850KXZE1M (FDC400 + FDC450)
- FDC900KXZE1M (FDC450 + FDC450)
- FDC950KXZE1M (FDC475 + FDC475)
- FDC1000KXZE1M (FDC500 + FDC500)
- FDC1060KXZE1M (FDC500 + FDC560)
- FDC1120KXZE1M (FDC560 + FDC560)
Specifications
Item | Unit | FDC735KXZE1M | FDC800KXZE1M | FDC850KXZE1M | FDC900KXZE1M | FDC950KXZE1M | FDC1000KXZE1M | FDC1060KXZE1M | FDC1120KXZE1M | |||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Nominal Horse Power | 26HP | 28HP | 30HP | 32HP | 34HP | 36HP | 38HP | 40HP | ||||
Power Source | 3 Phase-3wire 220V, 60Hz | |||||||||||
Starting Current | A | 10 | 16 | |||||||||
Max Current | A | 53.2 | 64 | 84.8 | ||||||||
Nominal Capacity | Cooling | kW | 73.5 | 80.0 | 85.0 | 90.0 | 95.0 | 100.0 | 106.0 | 112.0 | ||
Heating | 82.5 | 90.0 | 95.0 | 100.0 | 106.0 | 112.0 | 119.0 | 126.0 | ||||
Electrical Characteristics | Power Consumption | Cooling | kW | 19.92 | 21.92 | 24.94 | 27.96 | 27.96 | 27.94 | 30.59 | 33.24 | |
Heating | 19.73 | 21.38 | 23.19 | 25.00 | 26.00 | 26.98 | 29.44 | 31.90 | ||||
Exterior Dimensions | HxWxD | mm | 2048x2700x720 | |||||||||
Net Weight | kg | 587 | 642 | 734 | ||||||||
Refrigerant Charge | R410A | kg | 11.0+11.5 | 11.5x2 | ||||||||
Refrigerant Piping Size | Liquid Line | mm (in) | ⌀15.88 (5/8") | ⌀19.05 (3/4") | ||||||||
Gas Line | ⌀31.75 (1 1/4") [⌀34.92 (1 3/8")] | ⌀38.1 (1 1/2") [⌀34.92 (1 3/8")] | ||||||||||
Capacity Connection | % | 50~130 | ||||||||||
Number of Connectable Indoor Units | 63 | 69 | 73 | 78 | 80 |