MHI KXZ ODU3
From Technical Support Wiki
This is the support page for the Heat Pump outdoor units for MHI VRF air conditioners.
Heat Pump Systems (FDC) | |
Voltage | 220V |
---|---|
Capacities (kW) | 28.0-33.5 |
Heat Pump? | Yes |
Model Numbers
- FDC280KXZE1M
- FDC335KXZE1M
Specifications
Item | Unit | FDC280KXZE1M | FDC335KXZE1M | |||
---|---|---|---|---|---|---|
Nominal Horse Power | 10HP | 12HP | ||||
Power Source | 3 Phase 3 wiring 220V, 60Hz | |||||
Starting Current | A | 5 | ||||
Max Current | A | 33 | ||||
Nominal Capacity | Cooling | kW | 28.0 | 33.5 | ||
Heating | 31.5 | 37.5 | ||||
Electrical Characteristics | Power Consumption | Cooling | kW | 7.24 | 8.96 | |
Heating | 7.28 | 9.04 | ||||
Exterior Dimensions | HxWxD | mm | 1690x1350x720 | |||
Net Weight | kg | 266 | ||||
Sound Pressure Level | Cooling/Heating | dB(A) | 55/57 | 61/58 | ||
Refrigerant | Type/GWP | R410A/2088 | ||||
Charge | kg/TCO2Eq | 11.0/22.968 | ||||
Refrigerant Piping Size | Liquid Line | mm (in) | ⌀9.52 (3/8") | ⌀12.7 (1/2") | ||
Gas Line | ⌀22.22 (7/8") | ⌀25.4 (1") [⌀28.58 (1 1/8")] | ||||
Capacity Connection | % | 50~130 | ||||
Number of Connectable Indoor Units | 24 | 29 |