GMV Fresh Air Processing Type

From Technical Support Wiki
Jump to: navigation, search

This is the support page for the Fresh Air Processing Type indoor unit for Gree GMV VRF air conditioners.

Gree Electric Appliances VRF
Fresh Air Processing Type
Gree-GMV-Fresh-Air-Processing-Featured.png
Voltage 220V
Cooling Capacities (kW) 12.5-45.0
Heat Pump? Yes

Model Numbers

  • GMV-NDX125P/A-T
  • GMV-NDX140P/A-T
  • GMV-NDX224P/A-T
  • GMV-NDX250P/A-T
  • GMV-NDX280P/A-T
  • GMV-NDX450P/A-T

This series can be matched with GMV5, GMV5C, GMV5 CP, GMV5 Max and GMV5 HR (Top discharge outdoor unit)

Specifications

Model GMV-NDX125P/A-T GMV-NDX140P/A-T GMV-NDX224P/A-T GMV-NDX250P/A-T GMV-NDX280P/A-T GMV-NDX450P/A-T
Capacity Cooling kW 12.5 14.0 22.4 25.0 28.0 45.0
Heating kW 8.5 10.0 16.0 18.0 20.0 32.0
Power Supply V/Ph/Hz 220-240/1/50 & 208-230/1/60
Power Consumption W 350 350 760 860 860 1240
Airflow Volume (H/M/L) m3/h 1200/1000-2000 1200/1000-2000 2000/1500-3000 2500/2000-3500 2500/2000-3500 4000
CFM 706/589~1177 706/589~1177 1177/883~1766 1471/1177~2060 1471/1177~2060 2354
Rated Current Cooling A 1.5 1.5 2.5 3.1 3.1 3.4
Heating A 1.5 1.5 2.5 3.1 3.1 3.4
Water Heating A / / / / / /
ESP Pa 150/50~200 150/50~200 200/50~300 200/50~300 200/50~280 200
Sound Pressure Level (H/M/L) dB(A) 40~50 40~50 45~54 47~54 47~54 58
Connecting Pipe Diameter Liquid mm ⌀9.52 ⌀9.52 ⌀9.52 ⌀9.52 ⌀9.52 ⌀12.7
Gas mm ⌀15.9 ⌀15.9 ⌀19.05 ⌀22.2 ⌀22.2 ⌀28.6
Drain Pipe External Dia. mm ⌀25 ⌀25 ⌀30 ⌀30 ⌀30 ⌀33
Thickness mm 2.5 2.5 1.5 1.5 1.5 3.0
Dimension (WxDxH) Outline mm 1400x700x300 1400x700x300 1483x791x385 1483x791x385 1483x791x385 1700x1100x650
Package mm 1601x813x365 1601x813x365 1578x883x472 1578x883x472 1578x883x472 1893x1463x838
Net Weight/Gross Weight kg 54/61 54/61 82/104 82/104 82/104 208/266
Loading Quantity 40' GP set 84 84 52 52 52 16
40' HQ set 98 98 65 65 65 16