GMV5HR-ODU.png
Voltage 380V-415V
Cooling Capacities (kW) 22.4-45.0
Heat Pump? Yes

Model Numbers

  • GMV-Q224WM/E-X
  • GMV-Q280WM/E-X
  • GMV-Q335WM/E-X
  • GMV-Q400WM/E-X
  • GMV-Q450WM/E-X

Specifications

Model GMV-Q224WM/E-X GMV-Q280WM/E-X GMV-Q335WM/E-X GMV-Q400WM/E-X GMV-Q450WM/E-X
Capacity Range HP 8 10 12 14 16
Capacity Cooling kW 22.4 28.0 33.5 40.0 45.0
Heating kW 25.0 31.5 37.5 45.0 50.0
EER W/W 4.09 3.44 4.04 3.36 3.04
COP W/W 4.75 4.32 4.87 4.50 3.94
Power Supply V/Ph/Hz 380-415V 3Ph 50/60Hz
Max Circuit/Fuse Current A 16.3/20 20.9/25 24.7/32 28.8/40 33.2/40
Power Consumption Cooling kW 5.48 8.15 8.30 11.9 14.8
Heating kW 5.26 7.30 7.70 10.0 12.7
Maximum Drive IDU NO unit 13 16 19 23 26
Refrigerant Charge Volume kg 6.2 7.1 9.6 11.1 11.6
Sound Power Level dB(A) 82 84 85 90 90
Sound Pressure Level dB(A) 60 61 63 63 63
Connecting Pipe Diameter Liquid mm ⌀9.52 ⌀9.52 ⌀12.7 ⌀12.7 ⌀12.7
High Pressure Gas mm ⌀15.9 ⌀19.05 ⌀19.05 ⌀22.2 ⌀22.2
Low Pressure Gas mm ⌀19.05 ⌀22.2 ⌀25.4 ⌀25.4 ⌀28.6
Dimension (WxDxH) Outline mm 930x765x1605 930x765x1605 1340x765x1605 1340x765x1605 1340x765x1605
Package mm 1010x840x1775 1010x840x1775 1420x840x1775 1420x840x1775 1420x840x1775
Net Weight/Gross Weight kg 233/243 233/243 302/317 346/361 346/361
Loading Quantity 40' GP set 24 24 16 16 16
40' HQ set 24 24 16 16 16